Victron

91 Victron Energy B.V. | De Paal 35 | 1351 JG Almere | The Netherlands Autotransformer 32A 100A Input/output voltage 120 / 240V Input circuit breaker 32A, two pole 100A, two pole Frequency 50/60Hz Maximum 240 V feed through current 32A 100A Neutral current, 30 min 32A (3800 VA) Neutral current, continuous 28A @ 40ºC/100ºF Transformer type Toroidal Enclosure Aluminium Input circuit breaker yes Protection category IP21 Safety EN 60076 Weight 12,5 kg 13,5 kg Dimensions (h x w x d) 425 x 214 x 110 mm Autotransformer: schematic diagram Step-Up: 120VAC to 240VAC (Internal ground relay of inverter/charger may be used) Split phase: 120VAC to 120/240VAC (Internal ground relay of inverter/charger may be used) Stacked inverter balancing (Ground relay of autotransformer should be used) Generator Balancing (Neutral of generator should be connected to ground)