Victron

111 Victron Energy B.V. | De Paal 35 | 1351 JG Almere | The Netherlands General phone: +31 (0)36 535 97 00 | E-mail: sales@victronenergy.com www.victronenergy.com Connect (V) Delay Disconnect (V) Delay V < 13 V Remains open V < 11 V 0 sec 13,0 V < V < 13,2 V 10 min 11,0 V < V < 12,0 V 1 sec 13,2 V < V < 13,4 V 5 min 12,0 V < V < 12,2 V 10 sec 13,4 V < V < 13,6 V 1 min 12,2 V < V < 12,4 V 30 sec 13,6 V < V < 13,8 V 4 sec 12,4 V < V < 12,8 V 3 min > 12,8 V remains closed > 16 V over voltage disconnect Approximate connect and disconnect delay (multiply by two for a 24 V system) Cyrix-ct 12/24-120: connection diagram Cyrix-ct 12/24-230: connection diagram